Daikin · Furnace
E10 Grounding fault / poor neutral connection
What the control is telling you
The control detected a grounding error or a poor neutral connection. The furnace will not operate.
Applies to: Daikin DR96TN (upflow/horizontal) and DD96TN (downflow/horizontal) two-stage 96% furnaces with 9-speed ECM motor, R-32 ready
Likely causes
- Loose or high-resistance neutral connection
- Missing or poor ground path
Test and repair steps
- Check the neutral wire connection at the furnace junction box, the control board and the panel; tighten or repair.
- Verify continuity from the furnace to the ground source (ground wire back to the panel).
- Power off and measure neutral (white) to burner resistance - it should be very low (manual: less than 2 ohms).
- Restore power and confirm the code clears.
Settings for these units
- Normal status displays (7-segment) · Daikin DR96TN/DD96TN
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Daikin RSD6612304 (DR96TN/DD96TN service), 2 Stage Troubleshooting Codes, p.28-29. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.