Rinnai · Combi boiler
LC Lime condition – flush plate heat exchanger
What the control is telling you
Service reminder (when enabled in parameters) that the boiler is due for flushing and service. Lime build-up damages the plate heat exchanger and is not covered by warranty.
Applies to: I-Series Plus Combi boilers — 150K BTU and smaller and 175K BTU and higher
Likely causes
- Service interval reached
- Lime/scale build-up in the plate heat exchanger
- If it won't clear: DHW thermistor, flow sensor or boiler pump issue
Test and repair steps
- Shut off the gas supply and turn off the DHW and CH buttons on the controller.
- Close the hot and cold water shutoff valves (V3 and V4). Isolation valves are strongly recommended to allow flushing.
- Connect the pump outlet hose (H1) to cold water service valve V2 and the drain hose (H3) to hot water service valve V1.
- Put four gallons of undiluted, food-grade white vinegar in a pail and place the drain hose (H3) and pump inlet hose (H2) in it.
- Open service valves V1 and V2 and flush the plate heat exchanger with the circulating pump.
- Remove the front panel (two screws), locate the PC Board at lower left and press SW3 to clear the LC code.
- If LC does not clear, check the DHW thermistor, flow sensor and boiler pump.
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Rinnai Troubleshooting I-Series Plus Boiler Diagnostic Codes (800000375), p.46. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.