Rinnai · Combi boiler

670 Three-way valve fault

Medium severity I-Series Plus 150K and smallerI-Series Plus 175K and higher

What the control is telling you

The 3-way (DHW/CH) valve is in the wrong position, stuck, or the PC Board cannot communicate with it.

Applies to: I-Series Plus Combi boilers — 150K BTU and smaller and 175K BTU and higher

Likely causes

  • Loose, broken or damaged 3-way valve wiring
  • Wet harness or connectors
  • Poor CH system water quality
  • Valve stuck or mispositioned
  • Failed 3-way valve assembly

Test and repair steps

  1. Inspect the 3-way valve harness back to the PC Board for loose, broken or damaged connections and make sure it is dry.
  2. Check central heating system water quality.
  3. Warning: Live-voltage testing is dangerous and should only be done by qualified technicians using proper precautions.
  4. Read the valve position in performance data #15 (0 = mid, 1 = DHW, 2 = CH).
  5. At CN12, grey pin #16 to brown pin #18: under 1 VDC when fully open or closed, 4–6 VDC in mid position. Orange pin #6 to grey pin #16 should be 11–14 VDC.
  6. At CN12, pink pin #4 to red pin #3 and white pin #2 to blue pin #1 should each read 40–60 Ω.
  7. Replace the 3-way valve assembly if readings are out of spec or the fault remains.

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Rinnai Troubleshooting I-Series Plus Boiler Diagnostic Codes (800000375), p.37. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.