Rinnai · Combi boiler
443 Low water cut-off (LWCO) activated
What the control is telling you
The low water cut-off circuit has opened. The boiler uses a built-in pressure-sensor type LWCO (not serviceable or adjustable); an optional external LWCO can be wired to the PC Board.
Applies to: I-Series Plus boilers — 150K BTU and smaller and 175K BTU and higher (Combi and Solo)
Likely causes
- Low water level / pressure in the boiler
- Faulty internal or external LWCO device
- Missing LWCO jumper when using the built-in device
- Optional LWCO wired incorrectly
- No 24 VAC from transformer
- Failed transformer or PC Board
Test and repair steps
- Check local codes to confirm whether the built-in LWCO is acceptable; any optional LWCO probe must sit above the minimum safe water level and be wired to the proper PC Board terminal.
- Confirm the internal or external LWCO device is operating correctly.
- If relying on the built-in device, make sure the LWCO jumper is in place across its terminals.
- If using an optional LWCO, remove the jumper and connect the device to the three LWCO terminals.
- Check for 24 VAC transformer output at PC Board connector CN202 between red pin #2 and red pin #4.
- If 24 VAC is missing, check for 120 VAC at CN202 between white pin #1 and gray pin #3: if 120 VAC is present replace the transformer; if not, replace the PC Board.
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Rinnai Troubleshooting I-Series Plus Boiler Diagnostic Codes (800000375), p.29. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.