Rheem · Heat pump
L4 Locked rotor lockout
What the control is telling you
Compressor ran less than 15 seconds on four (4) consecutive starts during the same call; the ICC locks out the compressor (display flashes L then 04/4). Manual reset required. Reported as 4 flashes on the L terminal.
Applies to: (-)PRL-JEC 2-stage 16 SEER heat pumps: RPRL/UPRL-024JEC, -036JEC, -048JEC, -060JEC
Likely causes
- Bad run capacitor
- Low line voltage
- Excess refrigerant in compressor (flooding/migration)
- Seized compressor bearings
Test and repair steps
- Test the run capacitor and replace if out of spec.
- Measure line voltage at the compressor while starting; it must be within ±10% of nameplate (197-253V for 208/230V units).
- Make sure the crankcase heater works; at startup or after a long shutdown it should be powered 12 hours before starting the compressor.
- Check charge for overcharge/flooding.
- Check compressor windings for correct ohms and ground.
- Hard-start components are factory installed - verify they are intact.
- Reset the ICC after the cause is fixed press TEST for 1 second with an insulated probe (preferred), or cycle 24VAC (pull R or C) or cycle line power.
Settings for these units
- Outdoor unit clearances · Rheem/Ruud PRL-JEC heat pump (Comfort Control2 ICC)
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Rheem (-)PRL-JEC Heat Pump Installation Instructions, 12.4 Active Compressor Protection Mode / 12.6 ICC Diagnostic Codes, p.25, 29. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.