Rheem · Heat pump
Flashing c / C / h / H Anti-short-cycle (3 min) or minimum-run (30 s) timer active
What the control is telling you
A flashing mode letter means the ICC has a call (c = 1st-stage cool, C = 2nd-stage cool, h = 1st-stage heat pump, H = 2nd-stage heat pump) but is holding the compressor on its 3-minute anti-short-cycle timer or 30-second minimum-run timer. Not a fault. Note: some pages of this manual show h1/h2 instead of h/H.
Applies to: (-)PRL-JEC 2-stage 16 SEER heat pumps: RPRL/UPRL-024JEC, -036JEC, -048JEC, -060JEC
Likely causes
- Compressor recently stopped (3-minute delay between compressor runs)
- Call removed less than 30 seconds after start (minimum run timer)
Test and repair steps
- Wait for the timer to finish; the letter turns steady when the compressor runs.
- To skip the delay, press TEST for 1 second and release; display shows 't', then compressor and outdoor fan start.
- If the letter flashes repeatedly with constant short runs, check fault history for code 03 (short cycling).
Settings for these units
- Outdoor unit clearances · Rheem/Ruud PRL-JEC heat pump (Comfort Control2 ICC)
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Rheem (-)PRL-JEC Heat Pump Installation Instructions, 12.3 ICC Control Operation / 12.6 ICC Diagnostic Codes, p.23-25. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.