Rheem · Heat pump
90 Communication fault
What the control is telling you
Listed as 'Communication Fault' but the manual's description says the ICC has detected an internal fault and should be replaced - manual inconsistency.
Applies to: (-)PRL-JEC 2-stage 16 SEER heat pumps: RPRL/UPRL-024JEC, -036JEC, -048JEC, -060JEC
Likely causes
- Communication wiring problem (1/2 data wires)
- ICC internal fault
Test and repair steps
- Check data wires 1 and 2, R and C at the thermostat, indoor and outdoor units - reversed comm wires keep the green comm LED (D52) on solid.
- Check term/bus dip switches on the ICC and air handler (term switches ON).
- Never use phone cord or connect the system to a phone line.
- If wiring is correct, replace the ICC (move the memory card to the new board).
Settings for these units
- Outdoor unit clearances · Rheem/Ruud PRL-JEC heat pump (Comfort Control2 ICC)
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Rheem (-)PRL-JEC Heat Pump Installation Instructions, 12.6 ICC Diagnostic Codes, p.30. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.