Rheem · Heat pump

09 Low secondary (control) voltage

Medium severity Rheem/Ruud PRL-JEC heat pump (Comfort Control2 ICC)

What the control is telling you

Voltage between R and C at the ICC is below 18VAC. Reported as 9 flashes on the L terminal.

Applies to: (-)PRL-JEC 2-stage 16 SEER heat pumps: RPRL/UPRL-024JEC, -036JEC, -048JEC, -060JEC

Likely causes

  • Control transformer overloaded
  • Low line voltage

Test and repair steps

  1. Measure 24VAC at R-C on the ICC with the system calling; it must be at least 18VAC.
  2. Check the indoor unit transformer size 40VA minimum (communicating air handler/furnace uses 50VA).
  3. Disconnect accessories one at a time to find an overload.
  4. Check thermostat wire gauge/length (no smaller than 18 AWG; see Table 6).
  5. Check incoming line voltage at the indoor unit.

Settings for these units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Rheem (-)PRL-JEC Heat Pump Installation Instructions, 12.6 ICC Diagnostic Codes, p.29. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.