Rheem · Heat pump
06 Compressor open start circuit
What the control is telling you
The ICC sees current in the run circuit but none in the start circuit. If this happens four (4) times in one compressor call the ICC locks out with L6. Reported as 6 flashes on the L terminal.
Applies to: (-)PRL-JEC 2-stage 16 SEER heat pumps: RPRL/UPRL-024JEC, -036JEC, -048JEC, -060JEC
Likely causes
- Damaged, wrong or miswired run capacitor
- Broken wire or loose connector in the start circuit
- Open start winding
Test and repair steps
- Check the run capacitor for damage, wrong value or miswiring.
- Check for broken wires, loose connectors or a miswired compressor.
- Check compressor windings for continuity.
- Check the start wire from ICC to compressor S terminal.
Settings for these units
- Outdoor unit clearances · Rheem/Ruud PRL-JEC heat pump (Comfort Control2 ICC)
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Rheem (-)PRL-JEC Heat Pump Installation Instructions, 12.6 ICC Diagnostic Codes, p.29. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.