Rheem · Furnace

d7 Blower manufacturer conflict (BLWR MFG CNFLCT)

High severity RGPE/RGLE

What the control is telling you

Memory card does not support the manufacturer of the installed blower motor. Thermostat also shows Call For Service / CHECK FURNACE to the homeowner.

Applies to: RGPE/RGLE 2-stage 80+

Likely causes

  • Unsupported replacement ECM motor
  • Wrong memory card

Test and repair steps

  1. Check whether the original memory card is attached to the IFC or inserted in connector J15.
  2. If the IFC was replaced, break the original memory card off the old control and insert it in J15 of the new one.
  3. Warning: Never swap memory cards or controls between furnaces or from a condenser/air handler - wrong data can cut heating airflow and trip the main limit.
  4. If the original card is lost, order the correct replacement memory card for this model from ProStock and insert it in J15.
  5. Communicating systems confirm the model in the furnace user menu under Unit Info matches the rating label.
  6. Confirm the replacement ECM motor is an approved part for this model.

Settings for these units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: RGPE/RGLE: Table 16 p.49 / Table 20; memory card rules p.38-39. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.