Rheem · Furnace
44 Low pressure switch closed (stuck)
What the control is telling you
Low-fire pressure switch (LPC) is closed when it should be open, before the inducer starts. The furnace will not start a heat cycle. RGPE/RGLE: thermostat shows Call For Service.
Applies to: 802P/80MDP (802PA050-150); RGPE/RGLE 2-stage 80+
Likely causes
- Pressure switch contacts welded
- Shorted or miswired switch wiring
- Water in switch or hose
Test and repair steps
- With the inducer off, check LPC contacts - must be open.
- Check switch wiring for a short.
- Check switch and hoses for water or moisture.
- Replace the switch if contacts stay closed.
Settings for these units
- Filter sizes as shipped, upflow (Table 19) · RGPE/RGLE
- Reduced clearance to combustibles, upflow/horizontal (Fig. 4) · Rheem/Ruud 802P / 80MDP 80% two-stage furnace (UT 1028-928 IFC)
- Reduced clearance to combustibles (Fig. 3 and 4) · RGPE/RGLE
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: 802P: 92-24161-146-02, Diagnostics and Fault Codes table, p.40, 51; RGPE/RGLE: Table 16 p.49 / Table 20. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.