Rheem · Furnace
22 Main limit open
What the control is telling you
Main high-limit circuit is open (supply air too hot / poor airflow). 802P/R95P: if open more than 150 seconds during a heat call, 61 and 22 alternate (dead blower) until it recloses. RGPE/RGLE: an open main limit can indicate excessive duct static; thermostat shows Call For Service / CHECK FURNACE.
Applies to: 802P/80MDP (802PA050-150); R95P (R95PA040-115); RGPE/RGLE 2-stage 80+
Likely causes
- Dirty or restricted filter or cooling coil
- Closed registers/dampers, undersized or restricted ducts, high static
- Blower problem: wrong speed tap, bad capacitor, dirty wheel, failing motor, low voltage
- Overfiring (high gas pressure, wrong orifice)
- Loose limit wiring
Test and repair steps
- Replace the filter and check the A/C coil and blower wheel for dirt.
- Check registers/dampers are open and ducts are adequate.
- Verify the blower runs on heat speed; check speed tap, capacitor, wheel and motor (RGPE/RGLE: ECM blower, see 60/61).
- Measure temperature rise and compare with the rating plate range.
- RGPE/RGLE check rise at both low and high fire; adjust SW3-1/SW3-2 heat rise if outside range.
- Check manifold pressure and orifice size for overfiring.
- Check wiring between IFC and all limits; replace a limit that is open at normal temperature.
Settings for these units
- Clearance to combustibles (all models) · R95P
- Filter sizes as shipped, upflow (Table 19) · RGPE/RGLE
- Reduced clearance to combustibles, upflow/horizontal (Fig. 4) · Rheem/Ruud 802P / 80MDP 80% two-stage furnace (UT 1028-928 IFC)
- Reduced clearance to combustibles (Fig. 3 and 4) · RGPE/RGLE
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: 802P: 92-24161-146-02, Diagnostics and Fault Codes table, p.40, 48, 51; R95P: Diagnostics and Fault Codes table, p.87 (PDF p.91); RGPE/RGLE: Table 16 p.49 / Table 20; Fig. 45 p.63; user menus p.52. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.