Rheem · Furnace

2 blinks Pressure switch circuit open

Medium severity Rheem (-)GRC/(-)GTC 90 PlusRheem 90RJ/90TJ 90 Plus

What the control is telling you

Green STATUS LED blinks 2 times: the air-proving (negative) pressure switch circuit did not close or opened while the inducer was running.

Applies to: Rheem (-)GRC upflow and (-)GTC downflow/horizontal 90 Plus condensing gas furnaces (UT Electronic Controls 1012-925 / 1028-928 and Invensys ICC-H1MC7-01 IFC); Rheem 90RJ and 90TJ 90 Plus condensing gas furnaces (UT Electronic Controls 1012-925 or Invensys ICC-H1MC7-01 IFC, hot surface ignition)

Likely causes

  • Blocked vent or intake, or vent too long / too many elbows / too small
  • Blocked heat exchanger
  • Pressure switch hoses kinked, disconnected, or holding water
  • Inducer (IDM) wired wrong, weak, or bad capacitor
  • High wind opening the switch
  • On downflow 90+ units, auxiliary limit open (inducer wire runs through it)
  • Faulty pressure switch or wiring

Test and repair steps

  1. Warning: Hazardous line voltage - disconnect power before servicing; work must be done by a trained, qualified service technician.
  2. Confirm the inducer runs for the 30-second pre-purge; if not, check line voltage at the IDM, wires between IDM and IFC, line voltage on the IDM pins of the IFC connector, and the IDM capacitor (90+ only).
  3. Check the pressure switch(es), hoses and wires; drain any water or moisture from switches and hoses.
  4. Inspect vent and intake for blockage; verify vent length, number of elbows and pipe diameter are within the venting tables.
  5. Check for a blocked heat exchanger.
  6. Make sure the inducer is wired correctly and consider excessive wind at the termination opening the switch.
  7. On downflow 90+ models check the auxiliary limit - it should be closed.
  8. Watch for intermittent pressure switch operation during the ignition trial.

Settings for these units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Rheem (-)GRC/(-)GTC Installation Instructions 92-24161-88-00, Figure 56 IFC Troubleshooting Guide, p.54 (printed); Rheem 90RJ/90TJ Installation Instructions 92-24161-32-08, Figure 53 IFC Troubleshooting Guide, p.54 (printed p.53). Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.