Navien · Tankless water heater
E760 Flushing / service alarm
What the control is telling you
Service reminder: the scheduled service or descaling interval has run out.
Applies to: Navien NPE-A2 (built-in recirculation) and NPE-S2 condensing tankless water heaters: NPE-150S2, NPE-180A2/S2, NPE-210A2/S2, NPE-240A2/S2
Likely causes
- Service notification time reached (default 1,820 days)
- Descaling reminder interval reached
Test and repair steps
- Perform routine service flush the heat exchanger and clean the inlet water, recirculation inlet and air intake filters.
- Check water hardness and recommend a softener or PeakFlow if above 7 grains/gal.
- Adjust the interval if needed Installer Menu > 4. Service Notif Time (0-3,650 days) or Parameter 13. Descaling Reminder (No Alarm/6/12/24 months).
- Reset with the Back button after service.
Settings for these units
- Installation clearances (indoor / outdoor) · Navien NPE-2
- Water quality limits and flushing schedule · Navien NPE-2
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Navien NPE-A2/S2 User's Information Manual (20049624A), 5.2 Understanding Error Codes, p.18. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.