Navien · Tankless water heater
E110 Abnormal air pressure
What the control is telling you
The air pressure sensor (APS) detected a blocked or restricted air path.
Applies to: Navien NPE-A2 (built-in recirculation) and NPE-S2 condensing tankless water heaters: NPE-150S2, NPE-180A2/S2, NPE-210A2/S2, NPE-240A2/S2
Likely causes
- Clogged air intake filter
- Blocked exhaust or intake (debris, snow, ice, nests)
- Vent run too long or too many elbows
Test and repair steps
- Make sure the exhaust pipe and termination are clear (manual's listed action).
- Clean the air intake filter (the manual says a clogged filter causes Error 110).
- Check vent length max 75 ft with 2 in. (6 elbows), 150 ft with 3 in. or 4 in. (8 elbows); subtract 8 ft per 90 deg elbow on 2 in., 5 ft on 3 in. or 4 in.
- Make sure terminations are at least 12 in. above the highest expected snow line.
- Check Status Information > 14. Current APS (APS voltage).
- Reset once with the Back button on the front panel and note whether the code returns.
- Code back after a reset? Stay at the unit and phone Navien Technical Support, 1-800-519-8794.
Settings for these units
- Installation clearances (indoor / outdoor) · Navien NPE-2
- Water quality limits and flushing schedule · Navien NPE-2
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Navien NPE-A2/S2 User's Information Manual (20049624A), 5.2 Understanding Error Codes, p.17. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.