Navien · Combi boiler

E777 Low water cutoff (LWCO) activated

High severity Navien NCB-HNavien NFC-H

What the control is telling you

The external LWCO device has opened (low water in the system). NFC-H manual lists the reset type as: Auto reset.

Applies to: Navien fire-tube combi boilers, NFC-H series (NFC-250/200H, NFC-250/175H) and NCB-H combi boilers (NCB-250/150H, NCB-240/130H, NCB-240/110H, NCB-190/080H, NCB-190/060H)

Likely causes

  • Low system water level
  • External LWCO wiring
  • LWCO fault

Test and repair steps

  1. Inspect the LWCO wiring. The boiler puts out 24 VAC on the LWCO terminals (CNC3).
  2. Make sure the system water level/pressure is correct.
  3. Top up the system with make-up water as required.
  4. Test the LWCO per its own instructions (annual inspection may be required).

Settings for these units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Navien NCB-H Installation & Operation Manual, 11.7 Understanding Error Codes, p.129-130; Navien NFC-H Installation Manual, 11.7 Understanding Error Codes, p.127-128. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.