Navien · Combi boiler

E517 DIP switch setting fault

Medium severity Navien NCB-HNavien NFC-H

What the control is telling you

The DIP switch settings are invalid or inconsistent. NFC-H manual lists the reset type as: Manual reset.

Applies to: Navien fire-tube combi boilers, NFC-H series (NFC-250/200H, NFC-250/175H) and NCB-H combi boilers (NCB-250/150H, NCB-240/130H, NCB-240/110H, NCB-190/080H, NCB-190/060H)

Likely causes

  • DIP switch set to an unused combination
  • NFC-H: model DIP switches SW1 5&6 not matching the model

Test and repair steps

  1. Warning: turn power off before touching the DIP switches.
  2. Check DIP SW1 and SW2 against the DIP switch tables (SW1 1&2 OFF/OFF for normal operation; SW2 5&6 OFF/OFF for US/Canada).
  3. NFC-H SW1 5&6 = OFF/OFF for NFC-250/200H, ON/OFF for NFC-250/175H.
  4. Code keeps returning? Phone Navien Technical Support, 1-800-519-8794.

Settings for these units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Navien NCB-H Installation & Operation Manual, 11.7 Understanding Error Codes, p.129-130; Navien NFC-H Installation Manual, 11.7 Understanding Error Codes, p.127-128. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.