Navien · Combi boiler

E030 Exhaust overheat (abnormal exhaust temperature)

High severity Navien NCB-HNavien NFC-H

What the control is telling you

Flue gas temperature went above the control limit (the boiler limits exhaust to about 149°F (65°C) when PVC venting is selected). NFC-H manual lists the reset type as: Manual reset / Alarm.

Applies to: Navien fire-tube combi boilers, NFC-H series (NFC-250/200H, NFC-250/175H) and NCB-H combi boilers (NCB-250/150H, NCB-240/130H, NCB-240/110H, NCB-190/080H, NCB-190/060H)

Likely causes

  • High return water temperature with exhaust temperature control enabled
  • Scaled heat exchanger / poor heat transfer
  • Faulty exhaust temperature sensor

Test and repair steps

  1. Check Status Information > 24. Exhaust Temp and return temperature.
  2. If the system needs return water hotter than 140°F (60°C), DIP SW2 #8 must be set ON - and then the exhaust must be CPVC, polypropylene or stainless steel, not PVC.
  3. Warning: never set DIP SW2 #8 ON with PVC exhaust venting.
  4. Check the heat exchanger for scale and flush if needed.
  5. Code keeps returning? Phone Navien Technical Support, 1-800-519-8794.

Settings for these units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Navien NCB-H Installation & Operation Manual, 11.7 Understanding Error Codes, p.129-130; Navien NFC-H Installation Manual, 11.7 Understanding Error Codes, p.127-128. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.