Navien · Boiler
E736 Cascade communication fault
What the control is telling you
The main and sub boilers lost communication. Manual action: check the cascade cable.
Applies to: Navien NHB-H (NHB-055H/080H/110H/150H) and NFB-H fire-tube (NFB-175H/200H) condensing boilers
Likely causes
- Ready-Link cable loose or damaged at CNK1
- Sub unit not registered / IDs lost
- Sub unit powered off
Test and repair steps
- Warning: Turn off power to all boilers before reconnecting cables.
- Check the Ready-Link communication cables at the CNK1 terminal on each boiler (up to 16 boilers).
- Power all boilers on, then on the main unit run Cascade Status and Settings > 1. Cascade System Setting to reassign IDs.
- Use 2. Cascade System Removal on a sub with a network problem to drop it from the cascade.
- Check 7. Cascade Info for the status of each unit.
Settings for these units
- Installation clearances (indoor) · Navien NHB-H
- Installation clearances (indoor) · Navien NFB-H
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Navien NHB-H Installation and Operation Manual, 11.14 Understanding Error Codes, p.119; Navien NFB-H Installation Manual, 11.7 Understanding Error Codes, p.116; NHB-H User's Information Manual (V1.0 Apr 2024), 5.2, p.24. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.