Navien · Boiler
E352 High water pressure
What the control is telling you
System pressure is above the high limit. Manual action: check water pressure.
Applies to: Navien NHB-H (NHB-055H/080H/110H/150H) and NFB-H fire-tube (NFB-175H/200H) condensing boilers
Likely causes
- Expansion tank waterlogged, undersized or isolated
- Fill/pressure reducing valve letting by
- System overfilled
Test and repair steps
- Read Water Press in Status Info and compare with the system gauge.
- Check the expansion tank charge and size and that it cannot be isolated from the boiler.
- Check the pressure reducing / make-up valve is not over-pressurizing the system.
- NHB-H system pressure 12-30 psi with a 30 psi relief valve. NFB-H: 12-80 psi; parameter 17 High Sys Pressure (40-80 psi, default 50 psi) should suit the relief valve rating.
- Drain to the correct pressure and retest.
Settings for these units
- Installation clearances (indoor) · Navien NHB-H
- Installation clearances (indoor) · Navien NFB-H
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Navien NHB-H Installation and Operation Manual, 11.14 Understanding Error Codes, p.119; Navien NFB-H Installation Manual, 11.7 Understanding Error Codes, p.116; NHB-H User's Information Manual (V1.0 Apr 2024), 5.2, p.24. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.