E291 Return temperature higher than supply
What the control is telling you
Return water is hotter than supply water. Manual action: check for reversed piping.
Applies to: Navien NHB-H (NHB-055H/080H/110H/150H) and NFB-H fire-tube (NFB-175H/200H) condensing boilers
Likely causes
- Supply and return connections piped backwards
- Pump pumping in the wrong direction
- Reverse flow from another circuit (missing check valve)
Test and repair steps
- Verify the supply and return pipes are connected to the correct boiler connections.
- Check pump flow direction and that check valves are installed at pump outlets.
- Compare Supply Temp and Return Temp in Status Info while firing.
- Check for reverse flow during pump off-cycles from other pumps in the system.
Settings for these units
- Installation clearances (indoor) · Navien NHB-H
- Installation clearances (indoor) · Navien NFB-H
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Navien NHB-H Installation and Operation Manual, 11.14 Understanding Error Codes, p.119; Navien NFB-H Installation Manual, 11.7 Understanding Error Codes, p.116; NHB-H User's Information Manual (V1.0 Apr 2024), 5.2, p.24. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.