Navien · Boiler

E218 Heating return temperature sensor

Medium severity Navien NHB-HNavien NFB-H

What the control is telling you

Return water sensor fault. Manual action: check the thermistor connector.

Applies to: Navien NHB-H (NHB-055H/080H/110H/150H) and NFB-H fire-tube (NFB-175H/200H) condensing boilers

Likely causes

  • Loose or damaged return thermistor connector
  • Failed sensor

Test and repair steps

  1. Warning: Power off. Reseat the return thermistor connector and inspect wiring.
  2. Compare Return Temp in Status Info with actual pipe temperature.
  3. Replace the sensor if the reading is wrong.

Settings for these units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Navien NHB-H Installation and Operation Manual, 11.14 Understanding Error Codes, p.119; Navien NFB-H Installation Manual, 11.7 Understanding Error Codes, p.116; NHB-H User's Information Manual (V1.0 Apr 2024), 5.2, p.24. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.