Navien · Boiler
E109 Fan motor fault
What the control is telling you
The combustion fan is not reaching or holding the target speed. Manual action: check the fan and venting.
Applies to: Navien NHB-H (NHB-055H/080H/110H/150H) and NFB-H fire-tube (NFB-175H/200H) condensing boilers
Likely causes
- Fan wiring or hall sensor fault
- Fan motor failure
- Excessive vent restriction or blocked intake
Test and repair steps
- Run Test Mode > 1. Fan Motor; the fan should ramp up to top speed then back down.
- Compare Fan Target RPM with Fan Current RPM and Target/Current APS voltage in Status Info.
- Inspect venting and intake for blockage and confirm length/elbows are within limits.
- Clean the air intake filter.
- Warning: Power off, then check the fan connector and harness; replace the fan if it fails the test.
Settings for these units
- Installation clearances (indoor) · Navien NHB-H
- Installation clearances (indoor) · Navien NFB-H
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Navien NHB-H Installation and Operation Manual, 11.14 Understanding Error Codes, p.119; Navien NFB-H Installation Manual, 11.7 Understanding Error Codes, p.116; NHB-H User's Information Manual (V1.0 Apr 2024), 5.2, p.24. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.