Midea · Furnace
LED2 green 4 flashes Refrigerant sensor expired or faulty
What the control is telling you
The refrigerant sensor has reached end of life or is faulty. The Y signal is turned off and cooling stops.
Applies to: Midea BGH96M 96% AFUE two-stage gas furnaces (060B3A, 080B3A, 080C4A, 100C5A, 100D5A, 120D5A) with A2L refrigerant leak sensor on CN30 (fan drive board LED2)
Likely causes
- Sensor end of service life
- Sensor failure
Test and repair steps
- Confirm the sensor cable and CN30 connection are good.
- Order and install a new refrigerant detection sensor from the distributor.
- Confirm SW1-2 is ON and cooling resumes.
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Midea 96% AFUE Gas Furnace (A2L) Troubleshooting Guide, Appendix A3 Requirements for refrigerant leakage sensors, LED2 table, p.27. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.