Lennox · Furnace
E401 LSOM - long run or low pressure
What the control is telling you
Compressor ran more than 18 hours on one demand; also tracks low pressure switch trips. Critical alert.
Applies to: EL296UHV(X) series furnaces with integrated control 103130-XX only
Likely causes
- Low refrigerant charge
- Undersized system / high load
Test and repair steps
- Check system charge and low pressure switch operation.
- Check for airflow or load problems.
- Clears after 30 consecutive normal cycles or power reset.
Settings for these units
- Recommended filter size by cabinet width · EL296UHV
- Recommended filter size by cabinet width · Lennox SL280UHV
- Filter sizes by cabinet width · Lennox SL297NV
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Lennox EL296UHV(X) Unit Information / Service Literature, Table 5 Ignition Control 103130-XX Diagnostic Codes, p.37. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.