Lennox · Furnace
E276 Watchguard calibration failure
What the control is telling you
Pressure switch calibration failed; 1-hour soft lockout.
Applies to: EL296UHV(X) series furnaces with integrated control 103130-XX only
Likely causes
- Vent system problem
- Pressure switch wiring fault
Test and repair steps
- Inspect vent and intake piping for restrictions.
- After snow, ice or freezing fog, check intake and exhaust terminations and remove any obstruction.
- Check pressure switch wiring and connections.
- Check the condensate trap and the condensate hose screens at the cold end header box for blockage (power off; twist and pull screens, rinse); prime the trap with 10 fl. oz. (300 ml) of water if dry. If furnace and coil drains are combined, the A/C drain must be vented or the pressure switch will not work properly.
- Check hoses and inducer operation.
- Clears when calibration finishes successfully.
Settings for these units
- Recommended filter size by cabinet width · EL296UHV
- Recommended filter size by cabinet width · Lennox SL280UHV
- Filter sizes by cabinet width · Lennox SL297NV
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Lennox EL296UHV(X) Unit Information / Service Literature, Table 5 Ignition Control 103130-XX Diagnostic Codes, p.36, Maintenance p.87. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.