Lennox · Furnace
E273 Soft lockout - recycles exceeded, flame failure
What the control is telling you
Last recycle was due to loss of flame.
Applies to: EL296UHV(X) series furnaces (integrated control 103130-XX and 107045-XX)
Likely causes
- Dirty flame sensor
- Poor ground
- Gas supply fluctuation
Test and repair steps
- Enter Flame Signal mode hold the diagnostic push button until a solid F shows, release, and read flame current in microamps.
- Compare 2.6 uA or more is normal, 2.5 uA or less is low, and the flame drops out at 1.1 uA.
- Warning: Turn off power and gas before removing the flame sensor from the left side of the burner support.
- Clean the sensor rod (remove oxide) or replace it if damaged or still weak after cleaning.
- Measure neutral-to-ground voltage and verify the furnace has a solid earth ground; the control is polarity sensitive.
- Check ground at the control AC volts between line neutral and the C terminal should not exceed 2 VAC at idle, 5 VAC with inducer/ignitor on, 10 VAC with blower on; a wide swing under load means a poor ground. Line hot to neutral should be 97-132 VAC.
- Check gas pressures with a manometer supply natural gas 4.5-13.0 in. w.c. (LP 11.0-13.0); manifold natural 1.7 low fire / 3.5 high fire (LP 4.5 / 10.0) at 0-4500 ft.
- Clean burners if dirty (soft brush vacuum on burner faces) and confirm burners are centered in the burner ports.
- Run a heat cycle and confirm stable flame current.
Settings for these units
- Recommended filter size by cabinet width · EL296UHV
- Recommended filter size by cabinet width · Lennox SL280UHV
- Filter sizes by cabinet width · Lennox ML180UHE
- Filter sizes by cabinet width · Lennox SL297NV
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Lennox EL296UHV(X) Unit Information / Service Literature, Table 5 Ignition Control 103130-XX Diagnostic Codes, p.36; Ignition Control 107045-XX Diagnostic Codes table, p.43, Heating System Service Checks p.82-85, Maintenance p.88-89, Unit Components p.52. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.