Lennox · Furnace

E229 Ignition on high fire

Low severity EL296UHVLennox SL280UHVLennox SL297NV

What the control is telling you

Control switched to high-fire ignition because the low-fire pressure switch did not close in time. Informational.

Applies to: EL296UHV(X) series furnaces (integrated control 103130-XX and 107045-XX)

Likely causes

  • Low supply voltage
  • Low outdoor temperature
  • Marginal low-fire pressure differential

Test and repair steps

  1. No repair is required for this code by itself.
  2. Sequence if the low-fire switch does not close, the inducer goes to high, the high-fire switch closes after the 15 s pre-purge and the furnace lights on high fire, switching to low fire after 10-20 seconds.
  3. If it repeats often, check line voltage (97-132 VAC hot to neutral) and supply voltage under load.
  4. Check the vent system and condensate drainage, and measure low-fire pressure switch differential against the set-point tables.

Settings for these units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Lennox EL296UHV(X) Unit Information / Service Literature, Table 5 Ignition Control 103130-XX Diagnostic Codes, p.35; Ignition Control 107045-XX Diagnostic Codes table, p.42, Wiring and Sequence of Operation p.93. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.