E226 High pressure switch failed closed

High severity EL296UHVLennox SL280UHVLennox SL297NV

What the control is telling you

High-fire pressure switch is closed when it should be open.

Applies to: EL296UHV(X) series furnaces (integrated control 103130-XX and 107045-XX)

Likely causes

  • Switch contacts stuck closed
  • Jumpered switch
  • Wiring short

Test and repair steps

  1. Warning: Remove any jumper; the pressure switch must never be bypassed.
  2. The control checks that the pressure switches are open before the inducer starts; a switch closed at that point blocks ignition.
  3. Check high pressure switch operation at the start of a heat call.
  4. Check wiring for shorts.
  5. Measure operating pressure and compare to the set-point tables.
  6. Check the condensate trap and the condensate hose screens at the cold end header box for blockage (power off; twist and pull screens, rinse); prime the trap with 10 fl. oz. (300 ml) of water if dry. If furnace and coil drains are combined, the A/C drain must be vented or the pressure switch will not work properly.
  7. Inspect vent and inducer; replace the switch if contacts are stuck.

Settings for these units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Lennox EL296UHV(X) Unit Information / Service Literature, Table 5 Ignition Control 103130-XX Diagnostic Codes, p.35; Ignition Control 107045-XX Diagnostic Codes table, p.42, Troubleshooting: Heating Sequence of Operation flowchart, p.110-112. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.