Lennox · Furnace
E207 Hot surface ignitor open
What the control is telling you
The control sensed an open ignitor circuit.
Applies to: EL296UHV(X) series furnaces (integrated control 103130-XX and 107045-XX)
Likely causes
- Failed ignitor
- Broken ignitor wiring or plug
Test and repair steps
- Warning: Disconnect power before handling the ignitor plug or ignitor.
- Unplug the 4-pin plug from the control and measure ohms across terminals 1 and 5; it should read 39 to 70 ohms.
- If the reading is 0 or infinite, separate the 2-pin jack-plug near the manifold and measure the ignitor directly (39 to 70 ohms).
- If the ignitor reads correctly at the jack-plug, repair the wiring between the plug and the control; if not, replace the ignitor.
- With power restored, check voltage at terminals 1 and 5 during the 20-second warm-up; it should be 120 volts +/- 10%.
- If voltage is low, check the supply voltage to the furnace.
- Check ground at the control AC volts between line neutral and the C terminal should not exceed 2 VAC at idle, 5 VAC with inducer/ignitor on, 10 VAC with blower on; a wide swing under load means a poor ground. Line hot to neutral should be 97-132 VAC. A poor ground can cause early ignitor failure.
- If wiring, voltage and ignitor are all good but there is no ignitor output, suspect the integrated control.
Settings for these units
- Recommended filter size by cabinet width · EL296UHV
- Recommended filter size by cabinet width · Lennox SL280UHV
- Filter sizes by cabinet width · Lennox SL297NV
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Lennox EL296UHV(X) Unit Information / Service Literature, Table 5 Ignition Control 103130-XX Diagnostic Codes, p.35; Ignition Control 107045-XX Diagnostic Codes table, p.42, Unit Components p.54, Proper Ground and Voltage p.85. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.