Lennox · Furnace

E161 Refrigerant leak sensor #2 wrong type

Medium severity Lennox ML180UHE

What the control is telling you

Sensor #2 is not a type approved for this application. Clears when a suitable sensor is detected; the blower then latches on for at least 5 minutes.

Applies to: ML180UHEK (R-454B era) single-stage 80% furnaces with integrated control 107792-XX (ML180UH045/070/090/110/135, incl. low-NOx X models)

Likely causes

  • Non-approved or wrong replacement sensor installed on LGWP2

Test and repair steps

  1. Check the part number of sensor #2 against the approved sensor kit.
  2. Replace with a Lennox approved sensor.
  3. Press the LGWP test button to retest.

Settings for these units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Lennox ML180UHEK Unit Information 100161/100166, Table 6 Integrated Diagnostic Codes, p.14. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.