Lennox · Furnace
E155 Refrigerant leak sensor #2 communication lost
What the control is telling you
The control has lost communication with refrigerant detection sensor #2. The blower latches on for at least 5 minutes after communication returns.
Applies to: ML180UHEK (R-454B era) single-stage 80% furnaces with integrated control 107792-XX (ML180UH045/070/090/110/135, incl. low-NOx X models)
Likely causes
- Damaged or unplugged sensor #2 harness or connector
- Sensor #2 damaged or plug obstructed
- LGWP2 enabled with no second sensor fitted
Test and repair steps
- Confirm whether a second sensor is required/installed; if not, set LGWP2 to Disable.
- Check the sensor #2 cable at the LGWP2 plug for proper seating, damage or moisture.
- Inspect the harness route (right side grommet) for cuts or pinches.
- Press the LGWP test button to retest the fault after repair.
Settings for these units
- Filter sizes by cabinet width · Lennox ML180UHE
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Lennox ML180UHEK Unit Information 100161/100166, Table 6 Integrated Diagnostic Codes, p.14; Table 17, p.33. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.