E117 Poor ground detected

Medium severity EL296UHVLennox SL280UHVLennox ML180UHELennox SL297NV

What the control is telling you

Warning only: the ground connection is marginal.

Applies to: EL296UHV(X) series furnaces (integrated control 103130-XX and 107045-XX)

Likely causes

  • Weak or high-resistance ground connection

Test and repair steps

  1. Warning: Disconnect power before tightening ground connections.
  2. Inspect and tighten ground connections at the furnace and panel.
  3. Check ground at the control AC volts between line neutral and the C terminal should not exceed 2 VAC at idle, 5 VAC with inducer/ignitor on, 10 VAC with blower on; a wide swing under load means a poor ground. Line hot to neutral should be 97-132 VAC.
  4. Verify proper earth ground to the system.
  5. Warning clears 30 seconds after the fault is fixed.

Settings for these units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Lennox EL296UHV(X) Unit Information / Service Literature, Table 5 Ignition Control 103130-XX Diagnostic Codes, p.33; Ignition Control 107045-XX Diagnostic Codes table, p.40, Proper Ground and Voltage p.85. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.