Lennox · Furnace

E115 Low 24 VAC

High severity EL296UHVLennox SL280UHVLennox ML180UHELennox SL297NV

What the control is telling you

Control voltage is below range (normal range 18 to 30 volts). The control restarts once voltage recovers.

Applies to: EL296UHV(X) series furnaces (integrated control 103130-XX and 107045-XX)

Likely causes

  • Overloaded transformer from power-robbing accessories
  • Undersized transformer
  • Low line voltage

Test and repair steps

  1. Measure 24 VAC at the control; it should be between 18 and 30 volts.
  2. Check line voltage feeding the transformer.
  3. Look for extra accessories drawing from the 24 V circuit.
  4. Check the 3 A 24 V circuit breaker in the control box.
  5. Install a larger VA transformer if the load is too high; code clears when voltage recovers.

Settings for these units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Lennox EL296UHV(X) Unit Information / Service Literature, Table 5 Ignition Control 103130-XX Diagnostic Codes, p.33; Ignition Control 107045-XX Diagnostic Codes table, p.40. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.