Lennox · Furnace

-- Double dashes - zone sensor problem

Medium severity

What the control is telling you

Two dashes shown for indoor temperature on the S30/S40 or zone sensor: loose or miswired connections or two zone sensors on the same zone number. System runs central mode and individual zoning is disabled. S30/S40 thermostat / zone sensor display.

Applies to: Lennox communicating gas furnaces (e.g. SL280UHV/SL280UHNV, EL296UHV) in S30/S40 smart thermostat systems

Likely causes

  • Loose or incorrect zone sensor wiring
  • Duplicate zone number

Test and repair steps

  1. Check zone number assignments.
  2. Check and correct zone sensor wiring.
  3. Run the re-configuration procedure.

Settings for these units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Lennox Residential Communicating Systems Alert Code Guide (V2) 100017 (3/2023), Table 2 Alert Codes and Troubleshooting, p.51. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.