2 flashes Improper earth ground

Medium severity Lennox EL195UHNE

What the control is telling you

The control does not see a proper earth ground. Heat will not run; cooling continues. A poor ground also shortens ignitor life.

Applies to: EL195UHNE furnaces with ignition control 103217-03 or 107163-01 (red LED)

Likely causes

  • Missing or loose equipment ground
  • Poor ground at the panel

Test and repair steps

  1. Warning: Disconnect power before working on ground connections.
  2. Check the green ground wire at the furnace and back to the panel; tighten connections.
  3. Check ground at the control AC volts between line neutral and the C terminal should be about 0.3 V (2 V max) at idle, 0.75 V (5 V max) with inducer/ignitor on, under 2 V (10 V max) with blower on; line hot to neutral should be 97-132 VAC.
  4. Repair the ground before operating the furnace if readings exceed the maximums.

Settings for these units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Lennox EL195UHNE Unit Information Corp 1801-L1 (rev 04/2024), Table 4 (103217-03) / Table 5 (107163-01) diagnostic codes, p.8-10; Table 22, p.45. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.