Lennox · Furnace
12 flashes Flame sensed with gas valve off
What the control is telling you
The control senses flame when the gas valve should be closed. Gas valve stays off, inducer on, blower on heating speed.
Applies to: EL195UHNE furnaces with ignition control 103217-03 or 107163-01 (red LED)
Likely causes
- Gas valve leaking through
- Gas valve energized by miswiring
- Flame sensor shorted to ground / control fault
Test and repair steps
- Warning: Shut off gas to the furnace (valve switch by hand only).
- Look for flame at the burner with no call for heat; if present the valve is leaking - replace it.
- Check the gas valve wiring (pins 9 and 12) for a short that powers the valve.
- Check the flame sensor wire for shorts; if no flame is present, replace the control.
Settings for these units
- Filter sizes (filter rack kits) · Lennox EL195UHNE
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Lennox EL195UHNE Unit Information Corp 1801-L1 (rev 04/2024), Table 4 (103217-03) / Table 5 (107163-01) diagnostic codes, p.8-10; flowchart p.51. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.