Lennox · Air handler
E348 Indoor relay Y2 fault
What the control is telling you
The indoor control did not see 24 VAC after relaying a Y2 compressor demand. S30/S40 thermostat alert code 348 (shown as E348 on the unit control display).
Applies to: Lennox communicating air handlers and EIM-equipped indoor units in S30/S40 smart thermostat systems
Likely causes
- Y2 relay failed (contacts did not close or coil did not energize)
Test and repair steps
- Measure 24 VAC on Y2 output during a second-stage cooling call.
- If no voltage, replace the control.
- Clears automatically once fixed.
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Lennox Residential Communicating Systems Alert Code Guide (V2) 100017 (3/2023), Table 2 Alert Codes and Troubleshooting, p.26. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.