Lennox · Air handler

E310 Discharge air temperature sensor problem

Medium severity

What the control is telling you

Problem with the discharge air temperature sensor (DATS). S30/S40 thermostat alert code 310 (shown as E310 on the unit control display).

Applies to: Lennox communicating air handlers and EIM-equipped indoor units in S30/S40 smart thermostat systems

Likely causes

  • Open or shorted sensor or wiring
  • Short/open in thermostat communication connections

Test and repair steps

  1. Check for shorts or opens in the communicating thermostat connections to all components.
  2. Compare DATS resistance with the temperature/resistance chart in the unit instructions.
  3. Replace the sensor if necessary.
  4. Note DATS on a damper control module or EIM does not generate this alert.
  5. Clears 30 seconds after recovery or after restart.

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Lennox Residential Communicating Systems Alert Code Guide (V2) 100017 (3/2023), Table 2 Alert Codes and Troubleshooting, p.25. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.