Lennox · Air handler

37 Cooling when not requested

High severity

What the control is telling you

Cooling has run 15 minutes or more with no call for cooling. S30/S40 alert code 37.

Applies to: Lennox communicating air handlers and EIM-equipped indoor units in S30/S40 smart thermostat systems

Likely causes

  • Welded contactor or stuck relay
  • Miswiring
  • Other active alert codes

Test and repair steps

  1. Run diagnostics and compare with what the equipment actually does (S30: Dealer Control Center > Diagnostics > Start Diagnostics; S40: Service Support Center > Diagnostics > Select All > Start).
  2. Look for other alert codes.
  3. Check all cooling equipment (contactor, Y relay) for the cause.
  4. Cycle power. Clears automatically once fixed.

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Lennox Residential Communicating Systems Alert Code Guide (V2) 100017 (3/2023), Table 2 Alert Codes and Troubleshooting, p.11. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.