Lennox · Air conditioner
E441 Inverter compressor slowdown - high compressor current (inverter code 14)
What the control is telling you
Compressor current near its limit; speed reduced by 4 Hz and ramp slowed to 5 Hz per 20 seconds. Usually at startup and normally needs no service (dealer information). Inverter LED flash code 14 (red 1 flash, green 4 flashes). S30/S40 thermostat alert code 441 (shown as E441 on the unit control display).
Applies to: Lennox communicating air conditioners incl. variable-capacity inverter units in S30/S40 smart thermostat systems
Likely causes
- Startup current rise
- High pressures
Test and repair steps
- If this keeps happening, look for other alert codes or high pressure trips.
- Clears automatically.
- Check inverter LEDs flash code 14 = red 1 flash, green 4 flashes. Normal inverter LEDs with no fault: red ON, green OFF.
Settings for these units
- Outdoor unit clearances · Lennox EL16KC1
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Lennox Residential Communicating Systems Alert Code Guide (V2) 100017 (3/2023), Table 2 Alert Codes and Troubleshooting, p.43. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.