Lennox · Air conditioner
E409 Outdoor control low 24 VAC
What the control is telling you
Secondary voltage at the outdoor control fell below 18 VAC; after 10 minutes the thermostat turns that unit off. S30/S40 thermostat alert code 409 (shown as E409 on the unit control display).
Applies to: Lennox communicating air conditioners incl. variable-capacity inverter units in S30/S40 smart thermostat systems
Likely causes
- Overloaded or weak transformer
- Long or undersized thermostat wire
- Loose connection
Test and repair steps
- Measure 24 VAC at the outdoor control.
- Check transformer load and wiring.
- Clears after voltage is above 20 VAC for two seconds or power reset.
Settings for these units
- Outdoor unit clearances · Lennox EL16KC1
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Lennox Residential Communicating Systems Alert Code Guide (V2) 100017 (3/2023), Table 2 Alert Codes and Troubleshooting, p.30. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.