Lennox · Air conditioner
E400 Compressor internal overload tripped
What the control is telling you
Y1 demand present but the compressor is not running; its internal overload has tripped. S30/S40 thermostat alert code 400 (shown as E400 on the unit control display).
Applies to: Lennox communicating air conditioners incl. variable-capacity inverter units in S30/S40 smart thermostat systems
Likely causes
- Compressor overheated
- Loss of power to the unit
- Low charge, high head pressure
Test and repair steps
- Check power to the outdoor unit.
- Let the compressor cool and check why the overload tripped (charge, airflow, pressures).
- Goes away when the RUN and START sensors both see current for two seconds or more, when service is removed, or on a power reset.
Settings for these units
- Outdoor unit clearances · Lennox EL16KC1
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Lennox Residential Communicating Systems Alert Code Guide (V2) 100017 (3/2023), Table 2 Alert Codes and Troubleshooting, p.29. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.