Lennox · Air conditioner

65537 Missing base (smart hub)

High severity

What the control is telling you

Base (mag-mount) not detected and alarm 65538 raised over 30 times; amber LED on smart hub. S30/S40 thermostat alert code 65537.

Applies to: Lennox communicating air conditioners incl. variable-capacity inverter units in S30/S40 smart thermostat systems

Likely causes

  • Mag-mount not wired or mounted
  • Loose wiring

Test and repair steps

  1. Mount and wire the mag-mount before powering up the smart hub.
  2. Clears once the base is detected for two seconds.

Settings for these units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Lennox Residential Communicating Systems Alert Code Guide (V2) 100017 (3/2023), Table 2 Alert Codes and Troubleshooting, p.47. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.