Lennox · Air conditioner
29 Over temperature protection (indoor above 90 F)
What the control is telling you
Indoor temperature is above 90 F (factory default) or rose above it during a heating or cooling call; heating is blocked until it drops below 90 F. S30/S40 thermostat alert code 29.
Applies to: Lennox communicating air conditioners incl. variable-capacity inverter units in S30/S40 smart thermostat systems
Likely causes
- Heating equipment stuck on (e.g. reversing valve)
- Thermostat sensor reading wrong
- Very hot space
Test and repair steps
- Check that no heating equipment is stuck ON (gas valve, electric heat, reversing valve).
- Verify the thermostat's temperature sensor reads correctly.
- Use cooling mode to bring the space below 90 F.
- Clears automatically once fixed.
Settings for these units
- Outdoor unit clearances · Lennox EL16KC1
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Lennox Residential Communicating Systems Alert Code Guide (V2) 100017 (3/2023), Table 2 Alert Codes and Troubleshooting, p.10. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.