Lennox · Air conditioner

12 Indoor unit not detected

High severity

What the control is telling you

The thermostat cannot find a Lennox communicating indoor unit (furnace or air handler) on the system. S30/S40 thermostat alert code 12.

Applies to: Lennox communicating air conditioners incl. variable-capacity inverter units in S30/S40 smart thermostat systems

Likely causes

  • No power to indoor unit
  • Open or loose R, i+, i-, C wire at mag-mount/subbase, smart hub or indoor control
  • EIM not configured as furnace or air handler (non-communicating indoor unit)
  • Failed indoor control

Test and repair steps

  1. Check for 24 VAC at the indoor control and look for a missing component.
  2. Check R, i+, i- and C at the mag-mount or subbase, smart hub and every communicating device; ohm the wires for continuity.
  3. Cycle power to the indoor unit first, then the thermostat.
  4. With a non-communicating indoor unit, make sure the equipment interface module is configured as air handler or furnace.
  5. S30 go to Menu > Settings > Advanced Settings, open View Dealer Control Center, then pick Equipment > Reset All Equipment. The thermostat will find every Lennox communicating device again.
  6. S40 go to Menu > Settings > Advanced Settings, open View Service Support Center, then Equipment Setting > Reset and pick Reset HVAC Equipment.
  7. Replace the indoor control if it still does not respond. Clears automatically once fixed.

Settings for these units

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: Lennox Residential Communicating Systems Alert Code Guide (V2) 100017 (3/2023), Table 2 Alert Codes and Troubleshooting, p.9. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.