Lennox · Air conditioner
10 Unknown device detected
What the control is telling you
Outside of commissioning, the thermostat found a device it does not know and put it in soft disable (two horizontal lines on furnace/air handler/outdoor 7-segment display; green LED 3 s on / 1 s off on damper module or EIM). S30/S40 thermostat alert code 10.
Applies to: Lennox communicating air conditioners incl. variable-capacity inverter units in S30/S40 smart thermostat systems
Likely causes
- A new communicating device was added after the original setup
- A control board was replaced and the system was not reconfigured
Test and repair steps
- Find the soft-disabled control (two horizontal lines on its display, or green LED 3 s on / 1 s off).
- Confirm the added device is Lennox communicating compatible.
- S30 go to Menu > Settings > Advanced Settings, open View Dealer Control Center, then pick Equipment > Reset All Equipment. The thermostat will find every Lennox communicating device again.
- S40 go to Menu > Settings > Advanced Settings, open View Service Support Center, then Equipment Setting > Reset and pick Reset HVAC Equipment.
- Clear reconfigure the system (code clears after reconfiguration).
Settings for these units
- Outdoor unit clearances · Lennox EL16KC1
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: Lennox Residential Communicating Systems Alert Code Guide (V2) 100017 (3/2023), Table 2 Alert Codes and Troubleshooting, p.8. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.