ICP · Furnace
LED steady ON Amber LED on solid - control lockout / wrong model plug
What the control is telling you
A solid (non-flashing) amber LED means the control has locked itself out. Flowchart says it auto-resets after 1 hour.
Applies to: ICP F9MAE / G9MAE modulating variable-speed condensing gas furnaces (060, 080, 100, 120 kBtu/h)
Likely causes
- Wrong or missing model plug PL4
- Flame sense circuit failure
- Gas valve relay stuck open
- Software check error
Test and repair steps
- Compare the model plug PL4 with the one shown on the rating plate; replace PL4 if wrong.
- Reset power to clear the lockout.
- If the solid LED returns after reset, replace the furnace control.
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: ICP (F/G)9MAE Service and Technical Support Manual 440 04 4700 00, Figure 16 Troubleshooting Chart, p.33. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.