ICP · Furnace

10 Line voltage polarity

Medium severity ICP (F/G)9MAE Modulating Furnace

What the control is telling you

Line voltage polarity is wrong (or furnace not grounded); furnace will not heat. On twinned units also check 24 V transformer phasing.

Applies to: ICP F9MAE / G9MAE modulating variable-speed condensing gas furnaces (060, 080, 100, 120 kBtu/h)

Likely causes

  • 115 V hot and neutral reversed
  • Missing earth ground
  • Twinned units with transformers out of phase

Test and repair steps

  1. Warning: Turn off power before rewiring.
  2. Check polarity at the furnace junction box: hot (BLK) and neutral (WHT) correct.
  3. Confirm a proper earth ground to the furnace and control.
  4. If twinned, check low-voltage (24 V) transformer phasing.

Save it for the next call

Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.

Open the app

Source: ICP (F/G)9MAE Service and Technical Support Manual 440 04 4700 00, Figure 16 Troubleshooting Chart, p.35. Summarized in our own words; check the original manual for your model.

Homeowner looking at this code? See what it means for you and when to call a technician.

For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.