FlowMax · Combi boiler
E12 DHW storage tank (cylinder) sensor fault
What the control is telling you
Only on units set up to heat an indirect storage tank (parameter 1 = 01 or 02). The tank sensor reads out of range; sensor is 10 kOhm at 25°C. Lead may be up to 8 m long.
Applies to: FLOWMAX-90, FLOWMAX-120
Likely causes
- Tank sensor faulty or wrong type
- Tank sensor wire disconnected or wet
Test and repair steps
- Confirm the unit is configured for a storage tank (parameter 1) - if no tank is installed, the setting may be wrong.
- Check the tank sensor lead and connection at the board; maximum lead length is 8 m.
- Measure the sensor about 10 kOhm at 25°C (77°F).
- Replace the sensor if faulty or incorrect.
- Restart and confirm the code clears.
Settings for these units
- Installation clearances · FlowMax condensing combi (FLOWMAX-90/120)
- Hot water scald risk by temperature · FlowMax condensing combi (FLOWMAX-90/120)
Save it for the next call
Star this code in the HVACopedia app and keep the whole library on your phone for jobs with no signal.
Source: FlowMax FLOWMAX-120 Instruction Manual, 6.10 Troubleshooting table, p.66; FlowMax FLOWMAX-120 Instruction Manual, 6.11 Diagnostics error code list, p.67. Summarized in our own words; check the original manual for your model.
Homeowner looking at this code? See what it means for you and when to call a technician.
For licensed technicians. Gas, electrical and refrigerant work must be done by a qualified, licensed person. Shut off power and gas before servicing, never bypass a safety control, and follow the manufacturer’s manual for the exact model; it and local codes always take priority. HVACopedia is not affiliated with any manufacturer; brand and model names only identify the equipment.